MXG461 Modulating control valves with magnetic actuator, PN16, external threadStock no. BPZ:MXG461..
Mixing and 2-port valves PN 16 with magnetic actuator for modulating control of chilled or low-temperature hot water systems in closed circuits. With positioning control, position feedback signal, spring return function and manual control.
Additional info
When used as a 2-port valve, port B must be closed off with the accessories (nut, cover, gasket) provided with the valve.
MXG461..P valves for media containing mineral oils (data sheet N4455)
MXG461.. valves are UL listed
Warning
CAUTION!
Valve may only be used as a mixing or 2-port valve, not as a diverting valve.
MXG461B Modulating control valves with magnetic actuator, PN16, external thread, DVGWStock no. BPZ:MXG461B..
Mixing and 2-port valves PN 16 with magnetic actuator for modulating control of DHW (mains water, water in open circuits), chilled water or low-temperature hot water.
With positioning control, position feedback signal, spring return function and manual control.
Additional info
MXG461B... valves are UL listed
Warning
CAUTION!
Valve may only be used as a mixing or 2-port valve, not as a diverting valve.
Attribute |
Value |
PN class |
PN 16 |
Operating voltage |
AC 24, DC 20...30 V |
Positioning signal |
DC 0...10, DC 2...10, DC 0...20, DC 4...20, DC 0...20 V |
Positioning time |
<2 s (faulty format) |
Spring return function |
A->AB closed |
Position feedback |
DC 0...10, DC 2...10, DC 0...20, DC 4...20 V |
Degree of protection |
IP31 |
Ambient temperature, operation |
-5...45 °C |
Mounting position |
Upright to horizontal |
Permissible operating pressure |
1600 kPa |
Leakage rate |
< 0.05 % of k<subscript>vs</subscript> value (faulty format) |
Leakage rate bypass |
< 0.2 % of k<subscript>vs</subscript> value (faulty format) |
Medium temperature |
-20...130 °C |
Valve characteristic |
Equal-percentage, Linear |
Stroke resolution ΔH/H100 |
1:1000 |
Material, valve body |
Red brass CC491K, low-lead amount |
Material, inside set |
CrNi steel |
Δpmax |
300 kPa |
Δps |
300 kPa |
Product conformity |
DVGW approved |
Product Variants
MXG461B15-0.6 - Mixing/2-port magnetic control valve, external thread, PN16, DN15, kvs 0.6, AC / DC 24 V, DC 0/2...10 V / 4...20 mA
MXG461B15-1.5 - Mixing/2-port magnetic control valve, external thread, PN16, DN15, kvs 1.5, AC / DC 24 V, DC 0/2...10 V / 4...20 mA
MXG461B15-3 - Mixing/2-port magnetic control valve, external thread, PN16, DN15, kvs 3, AC / DC 24 V, DC 0/2...10 V / 4...20 mA
MXG461B20-5 - Mixing/2-port magnetic control valve, external thread, PN16, DN20, kvs 5, AC / DC 24 V, DC 0/2...10 V / 4...20 mA
MXG461B25-8 - Mixing/2-port magnetic control valve, external thread, PN16, DN25, kvs 8, AC / DC 24 V, DC 0/2...10 V / 4...20 mA
MXG461B32-12 - Mixing/2-port magnetic control valve, external thread, PN16, DN32, kvs 12, AC / DC 24 V, DC 0/2...10 V / 4...20 mA
MXG461B40-20 - Mixing/2-port magnetic control valve, external thread, PN16, DN40, kvs 20, AC / DC 24 V, DC 0/2...10 V / 4...20 mA
MXG461B50-30 - Mixing/2-port magnetic control valve, external thread, PN16, DN50, kvs 30, AC / DC 24 V, DC 0/2...10 V / 4...20 mA |
|

|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Product Variants
MXG461.15-0.6 - Mixing/2-port magnetic control valve, external thread, PN16, DN15, kvs 0.6, AC / DC 24 V, DC 0/2...10 V / 4...20 mA
MXG461.15-1.5 - Mixing/2-port magnetic control valve, external thread, PN16, DN15, kvs 1.5, AC / DC 24 V, DC 0/2...10 V / 4...20 mA
MXG461.15-3.0 - Mixing/2-port magnetic control valve, external thread, PN16, DN15, kvs 3, AC / DC 24 V, DC 0/2...10 V / 4...20 mA
MXG461.20-5.0 - Mixing/2-port magnetic control valve, external thread, PN16, DN20, kvs 5, AC / DC 24 V, DC 0/2...10 V / 4...20 mA
MXG461.25-8.0 - Mixing/2-port magnetic control valve, external thread, PN16, DN25, kvs 8, AC / DC 24 V, DC 0/2...10 V / 4...20 mA
MXG461.32-12 - Mixing/2-port magnetic control valve, external thread, PN16, DN32, kvs 12, AC / DC 24 V, DC 0/2...10 V / 4...20 mA
MXG461.40-20 - Mixing/2-port magnetic control valve, external thread, PN16, DN40, kvs 20, AC / DC 24 V, DC 0/2...10 V / 4...20 mA